Two transformers are connected in parallel. These transformers do not have equal percentage impedance. This is likely to result in?

Show More Ask Question

1 Answer

Answer :

Two transformers are connected in parallel. These transformers do not have equal percentage impedance. This is likely to result in loading of the transformers not in proportion to their kVA ratings.

Like 0 like
Next Page →

Related

Answer : Necessary conditions required to be satisfied in order to ensure successful parallel operation of single phase transformers:  1. Only transformers having the same phase displacement between primary and secondary ... . 7. The phase sequence must be followed strictly on HV and LV side connection.

Description : An additional condition for parallel operation of three-phase transformers over single-phase transformers is that

Answer : An additional condition for parallel operation of three-phase transformers over single-phase transformers is that the transformers should belong to the same vector group

Description : If the percentage impedances of the two transformers working in parallel are different, then?

Answer : If the percentage impedances of the two transformers working in parallel are different, then parallel operation will still be possible, but the power factors at which the two transformers operate will be different from the power factor of the common load.

Description : Two transformers A and B having equal outputs and voltage ratios but unequal percentage impedances of 4 and 2 are operating in parallel. The transformer A will be overloaded by 

Answer : Two transformers A and B having equal outputs and voltage ratios but unequal percentage impedances of 4 and 2 are operating in parallel. The transformer A will be overloaded by 33%

Description : [75] Two transformers are connected in parallel. These transformers do not have equal percentage impedance which results A. Short-circuiting of the secondaries B. Power factor of one of the ... have negligible core losses D. Loading of the transformers not in proportion to their kVA ratings.

Answer : D. Loading of the transformers not in proportion to their kVA ratings