Answer :

For the parallel operation of single phase transformers, it is necessary that they should have same polarity.

Like 0 like

Answer :

Necessary conditions required to be satisfied in order to ensure successful parallel operation of single phase transformers: 

1. Only transformers having the same phase displacement between primary and secondary voltage can operate in parallel. The clock-hour which indicate the phase displacement is stamped on the transformer rating plate, e.g. Dyn11, Yd11, 2. Terminals with the same polarity on HV- and LV side shall be connected in parallel, 3. Transformers should have approximately the same voltage ratio, within +-0.05% 4. The short-circuit impedance voltage should be the same, within +-10%, 5. The power rating of the transformers should not deviate more than 1:3, 6. Tap changers should have tap position giving voltage ratios as close as possible. 7. The phase sequence must be followed strictly on HV and LV side connection.

Like 0 like
Next Page →

Related

Description : An additional condition for parallel operation of three-phase transformers over single-phase transformers is that

Answer : An additional condition for parallel operation of three-phase transformers over single-phase transformers is that the transformers should belong to the same vector group

Answer : For the parallel operation of two or more D.C. compound generators, we should ensure that series fields of all generators should be either on positive side or negative side of the armature.

Description : Two transformers are connected in parallel. These transformers do not have equal percentage impedance. This is likely to result in?

Answer : Two transformers are connected in parallel. These transformers do not have equal percentage impedance. This is likely to result in loading of the transformers not in proportion to their kVA ratings.

Description : Single phase transformer

Answer : Single phase Transformer Transformer