The secondary of a current transformer is always short-circuited under operating conditions because it?

1 Answer

The secondary of a current transformer is always short-circuited under operating conditions because it avoids core saturation and high voltage induction.

thumb_up_alt 0 like thumb_down_alt 0 dislike

Related questions

Description : When secondary of a current transformer is open-circuited its iron core will be?

Answer : When secondary of a current transformer is open-circuited its iron core will be hot because of heavy iron losses taking place in it due to high flux density.

Description : For a transformer, operating at constant load current, maximum efficiency will occur at?

Answer : For a transformer, operating at constant load current, maximum efficiency will occur at unity power factor.

Description : The operating point of a protective current transformer is near the

Answer : The operating point of a protective current transformer is near the Ankle point

Answer : In a D.C. shunt motor, under the conditions of maximum power, the current in the armature will be more than full-load current.

Description : In a transformer the resistance between its primary and secondary should be?

Answer : In a transformer the resistance between its primary and secondary should be infinity.

Description : Increasing the number of turns of wire on the secondary of a transformer will  (A) Decrease the secondary current (B) Increase the primary current (C) Have no effect on the secondary current (D) Increase the secondary current

Answer : Increasing the number of turns of wire on the secondary of a transformer will Decrease the secondary current 

Description : A certain transformer has 200 turns in the primary winding, 50 turns in the secondary winding and 120 volts applied to the primary. What is the voltage across the secondary?  (A) 30 Volts (B) 480 Volts (C) 120 Volts (D) 60 Volts

Answer : A certain transformer has 200 turns in the primary winding, 50 turns in the secondary winding and 120 volts applied to the primary. What is the voltage across the secondary?  (A) 30 Volts (B) 480 Volts (C) 120 Volts (D) 60 Volts

Description : The efficiency of two identical transformers under load conditions can be determined by?

Answer : The efficiency of two identical transformers under load conditions can be determined by back-to-back test.

Description : A 230 V/460 V single-phase transformer operating at 20 A and unity power factor has primary referred resistance of 0.2 Ω and reactance of 0.5 Ω. The approximate primary induced emf is (A) 216 V (B) 226 V (C) 234 V (D) 236 V

Answer : A 230 V/460 V single-phase transformer operating at 20 A and unity power factor has primary referred resistance of 0.2 Ω and reactance of 0.5 Ω. The approximate primary induced emf is 226 V

Answer : If the capacitor of a single-phase motor is short-circuited the motor will not start.

Answer : In case one phase of a three-phase synchronous motor is short-circuited the motor will not start.

Description : Even at no-load, a transformer draws current from the mains. Why?

Description : In a step-down transformer, there is a change of 15 A in the load current. This results in change of supply current of?

Answer : In a step-down transformer, there is a change of 15 A in the load current. This results in change of supply current of less than 15A.

Description : If an unsymmetrical line to ground fault occurs at the secondary terminals of a delta/star, ungrounded transformer, then  (A) zero sequence currents are present on both sides of the transformer  (B) ... side  (D) zero sequence currents are present on the primary side but not on the secondary side

Answer : If an unsymmetrical line to ground fault occurs at the secondary terminals of a delta/star, ungrounded transformer, then zero sequence currents are absent on both sides of the transformer 

Answer : The magnetising current of a transformer is usually small because it has small air gap.

Description : The efficiency of a transformer, under heavy loads, is comparatively low because?

Answer : The efficiency of a transformer, under heavy loads, is comparatively low because copper loss becomes high in proportion to the output.

Description : Step-down transformer converts high voltage and low current into:  (A) How voltage and high current (B) High voltage and low current (C) Low voltage and high current (D) None of the above

Answer : Step-down transformer converts high voltage and low current into: Low voltage and high current

Description : The inrush current of a transformer at no load is maximum if the supply voltage is switched on  (1) at peak voltage value (2) at zero voltage value (3) at half voltage value (4) at 0.866 time voltage value

Answer : At 0.866 time voltage value

Description : In a single-phase transformer, the magnetizing current is (A) in phase with the no-load current (B) in quadrature with the no-load current (C) the product of no-load current and power factor (D) in phase with the flux in the core

Answer : In a single-phase transformer, the magnetizing current is in phase with the flux in the core

Answer : The inverse definite mean time relays are used for over current and earth fault protection of transformer against internal short-circuits.

Description : How eddy current is produced in a transformer?

Description : Explain the concept of initial and final conditions in switching for L and C.

Answer : i) Inductor: The current through an inductor cannot change instantly. If the inductor current is zero just before switching, then whatever may be the applied voltage, just after switching the inductor ... open-circuit.  The initial and final conditions are summarized in following table:

Answer : An ideal transformer has infinite values of primary and secondary inductances. The statement is false.

Description : State why a transformer always have an efficiency of more than 90%.

Answer : As transformer is static device with no moving parts, the losses due to friction & windage are completely absent. Hence transformer has efficiency of more than 90%.

Description : During short circuit test iron losses are negligible because?

Answer : During short circuit test iron losses are negligible because the voltage applied on primary side is low.

Answer : A transformer cannot raise or lower the voltage of a D.C. supply because Faraday's laws of electromagnetic induction are not valid since the rate of change of flux is zero.

Answer : In an actual transformer the iron loss remains practically constant from no load to full load because core flux remains practically constant.

Description : Draw construction of Megger and write operating principle of it.

Answer : Megger:  Working: Two coils the current coil and pressure coil are mounted at an angle on the same spindle and form the part of the moving system. These coils are connected to a small hand driven ... . When the instrument is not working the pointer may rest at any position on the dial.

Answer : No-load current in a transformer lags behind the voltage by about 75°.

Answer : The no load current in a transformer lags behind the applied voltage by an angle of about 75°.

Answer : No-load current of a transformer has small magnitude and low power factor.

Description : Define: primary and secondary distribution system 

Answer : i) Primary Distribution:  It is a 3-phase, 3-wire transmission line connected in between receiving substation to Distribution substation. OR It is link between receiving substation & ... substation to consumer line. OR It is link between distribution transformer substation & consumer. 

Description : State the losses in secondary distribution system. 

Answer : The losses in secondary distribution system: a) Technical losses: 1. Due to poor voltage 2. Due to unbalance load 3. Due poor quality of transformer & its components 4. Due to poor quality ... of induction type of energy meter. 3. Lack of administration. 4. Energy theft 5. Unmetered supply

Description : State the meaning of secondary instrument. Classify secondary instruments.

Answer : Secondary instruments: - Gives reading directly of the quantity being measured. - Calibrated with respect to absolute instruments  Classification of Secondary instruments:  1. Depending on the ... on permissible error: i) Standard meters ii) Substandard meters iii) First grade instruments.

Description : State the meaning of absolute instrument and secondary instrument. 

Answer : Absolute instruments:   These instruments read the quantity under measurement indirectly i.e. in terms of deflection, degrees and meter constant. The actual value under measurement can be calculated ... of operation (b) Depending upon permissible percentage error. (c) Depending upon application.

Description : Why CT is never operated with an open secondary ?

Answer : CT secondary should never be kept open because it will cause saturation of the core to a high level and very high voltage will appear across the secondary which can breakdown the insulation. One terminal of PT secondary is always grounded to avoid capacitive induction and for human safety

Description : Compare primary and secondary instruments.

Answer : Primary instruments  Secondary instruments  Gives magnitude of quantity in terms of physical constants of instrument  Gives reading directly of the quantity measured.  Need no calibration  ... .  e.g. magnetic meter, induction meter, hotwire meter and electrostatic meter 

Description : Write difference between absolute & secondary instrument.

Answer : Absolute Instrument Secondary Instrument 1. These give magnitude of quantity in terms physical constants of instruments 1. These give reading directly of the quantity at the time of ... Raleigh current balance. 6. Examples - ammeter, voltmeter, amperehour meter, wattmeter etc.

Description : Which of the following connection of transformers will give highest value of secondary voltage ? (A) Delta primary delta secondary (B) Delta primary star secondary (C) Star primary star secondary (D) Star primary delta secondary

Answer : Which of the following connection of transformers will give highest value of secondary voltage ? (A) Delta primary delta secondary (B) Delta primary star secondary (C) Star primary star secondary (D) Star primary delta secondary

Description : What happens to the voltage in the secondary when the frequency of the supply in the primary is decreased? A) It increases B) It decreases C) It remains the same D) Cannot say unless the actual percentage increase in the frequency is known

Answer : What happens to the voltage in the secondary when the frequency of the supply in the primary is decreased? A) It increases B) It decreases C) It remains the same D) Cannot say unless the actual percentage increase in the frequency is known

Description : What do you mean by secondary instruments?

Answer : The instruments which will give the direct readings are called secondary instruments

Answer : Greater the secondary leakage flux less will be the secondary induced e.m.f.

Description :  operating principle of PUT.

Answer : Constructional diagram & Operating principle of PUT:  The PUT is a PNPN device similar to SCR, but its operation is similar to the UJT. The PUT behave like a UJT whose trigger voltage VP can be set ... low resistance and VAK ≈ 1V). The PUT is also referred to as a complementary SCR (CSCR). 

Description : Transistor operating configurations

Answer : Transistor operating configurations

Description : Explain the operating principle of LASER and list applications of LASER diode.

Answer : A basic construction of Laser diode is as shown . A PN junction is formed by two layers of doped gallium arsenide. There is highly reflective surface at one end of PN junction and ... 6. laser scanning and light beam illumination. 7. Military applications 8. Medical surgery 9.Diamond cutting

Description : The command line interpreter that enables the users to interact with operating system is called the A) Window B) Shell C) Process D) Kernel 

Answer : The command line interpreter that enables the users to interact with operating system is called the Shell 

Description : The operating time of instantaneous relay is

Answer : The operating time of instantaneous relay is 0.1 sec

Description : A minimum clearance of 6.3 m to ground is required for overhead lines when operating voltages are :  (A) less than 66 kV (B) lie between 66 kV and 110 kV (C) more than 165 kV (D) lie between 110 kV and 165 kV

Answer : A minimum clearance of 6.3 m to ground is required for overhead lines when operating voltages are : lie between 66 kV and 110 kV