What is the advantage of high power factor?

2 Answers

Due to high power factor, the current through the cable is reduced. Since current is inversely proportional to power factor. The cable area or diameter is reduced. This reduces unnecessary copper losses and initial constrctional cost of cable.

Also due to high pf, overloading of line is eradicated. It also increases the efficiency of transmission. It reduces the electricity bills as KVA amount is less due to high pf. It also avoids power factor penalties. These are applicable for ac circuits only.

 For dc circuits, pf does not play any role in power transmission.
Like 0 like Dislike 0 dislike
Reduced copper losses

Smaller conductor size

Improve voltage regulation

Increase system capability

Less energy bill
Like 0 like Dislike 0 dislike

Related questions

Description : Power factor of the system is kept high?

Answer : Power factor of the system is kept high to reduce line losses, to maximise the utilization of the capacities of generators, lines and transformers, to reduce voltage regulation of the line.

Answer : An induction motor has relatively high power factor at near full load.

Answer : For high value of diversity factor, a power station of given installed capacity will be in a position to supply more number of consumers.

Description : What is the use of power factor correction?

Description : What is the best power factor?

Answer : It is unity power factor but difficult to achieve in dynamic loads

Description : What is power factor angle?

Description : Can you have a power factor greater than 1?

Answer : We cannot have power factor greater than 1. As it is a measure of cosine of angle between voltage and current. 

Description : Why do we need to correct power factor?

Description : How do you measure power factor?

Answer : P= 1.83*V*I*[email protected] where P is power           V is voltage            I is current           COS @ is P.F [email protected]= P/(1.83*V*I)  in other way cos @ = true power/apparent power

Answer : High load factor indicates total plant capacity is utilised for most of the time.

Description : What is a high tension power line?

Answer : High tension power line is a high voltage of 115 kv and power line is underground transimissio used by urbun areas

Answer : The contacts of high voltage switches used in power system are submerged in oil. The main purpose of the oil is to extinguish the arc.

Description : Why high voltage can reduce power loss?

Answer : when voltage has increased due to reduced current flow, thus power loss given by ( I^2R) will be low due to reduced current(I^2) provided that resistance (R) is constant.

Description : Why high voltage is used in power transmission?

Answer : The primary reason that power is transmitted at high voltages is to increase efficiency. ... The lower current that accompanies high voltage transmissionreduces resistance in the conductors aselectricity flows ... This means that thin, light-weight wires can beused in long-distance transmission.

Description : What is the value of capacitance required to improve power factor from 0.7 to 0.9. Given that: Real power = 50 W Vrms of the source = 120 Frequency = 50 Hz   #powerfactor

Description : What is the power factor when a single phase watt meter operating on 200 V and 5 A for 5 hours makes 2016 revolutions and the meter constant in revolution is 420? A) 0.04 B) 1.04 C) 0.96 D) None of these

Answer : What is the power factor when a single phase watt meter operating on 200 V and 5 A for 5 hours makes 2016 revolutions and the meter constant in revolution is 420? A) 0.04 B) 1.04 C) 0.96 D) None of these

Description : What is the maximum value of power factor?

Answer : 1 is the maximum value of power factor.

Description : What is the power factor of purely resistive circuit.

Answer : Unity that is 1

Description : State the effects of low power factor on efficiency and voltage regulation of short transmission lines. 

Answer : i) Effect of Low power factor on efficiency:- When power factor of load reduces current drawn by transmission line increases so copper losses in transmission line increases, hence transmission ... increases, so voltage drop in transmission line increases so regulation increases. (Become Poor) 

Description : Briefly explain how the power factor of an inductive circuit can be improved.

Answer : As we know that power factor should be corrected to ensure that the current supplied is cost friendly. Meaning the power factor should be around one but not greater than one(0.8-0.9) in a ... an inductive circuit due to the inductive reactance which oppose the change of current in the ac circuit. 

Description : Why capacitors are used to improve power factor?

Answer :  Capacitors generate reactive power instead of that drawn from source which is required by inductive loads.so it reduce the reactive current which is drawn from source to be drawn from capacitor.This control in Electric bills cost.

Description : Discuss how power factor tariff results into energy conservation.

Answer : Power factor tariff results into energy conservation: i) Applying incentives and penalties according to power factor is an effective way, which enables consumer to improve power factor so that he can ... finally leads to reduction in the current drawn by the load and helps for energy conservation.

Description : Draw and explain bulk correction method for power factor & control.

Answer : Bulk correction method for power factor & control: i) Here individual starter controls the capacitors located at distribution panel. ii) Centralized compensation is employed in large industrial plants where many ... capacitor units in steps to maintain P.F. more than preset limit (0.95). 

Description : State the incentives and penalties related with power factor tariff.

Answer : Incentives and penalties related with power factor tariff: In addition to basic tariff (Maximum Demand Tariff / KVA Maximum Demand Tariff / Load factor tariff) the tariff in which P.F. of ... industrial consumer/H.T/ commercial consumers with contract demand above 80 kw/ 100Kva/107 hp consumer.

Description : With a neat sketch explain working of 1 phase dynamometer type power factor meter.

Answer : Working of 1 phase dynamometer type power factor meter : The current coil is connected in series with load. Two pressure coils marked as A and B are connected across the supply terminals ... becomes stationary and the pointer shows steady deflection corresponding to the power factor of the load. 

Description : State the significance of power factor.

Answer : Significance of power factor:-  1. Cosine of angle between voltage & current in a circuit is called power factor. 2. It is a measure of the real power in a circuit. 3. Inductive & ... KVA rating equipment 5. Greater conductor size 6. CosØ = R/Z  CosØ= Active Power/ Apparent Power 

Description : A transformer has negative voltage regulation when its load power factor is   (1) Zero (2) Unity (3) Leading (4) Lagging

Answer : Leading

Description : The power factor of dielectric :  (A) is a function of temperature of the dielectric only (B) depends only on voltage stress to which the dielectric is stressed (C) always constant (D) both (A) and (B)

Answer : The power factor of dielectric :  (A) is a function of temperature of the dielectric only (B) depends only on voltage stress to which the dielectric is stressed (C) always constant (D) both (A) and (B)

Description : Power station having Load factor = 70%, capacity factor = 50%, used factor = 60%, maximum demand = 20MW then annual energy production is  (1) 122.8 GWh (2) 198.55 GWh (3) 128.2 GWh (4) 188.82 GWh

Answer : Power station having Load factor = 70%, capacity factor = 50%, used factor = 60%, maximum demand = 20MW then annual energy production is 122.8 GWh

Description : In a synchronous generator delivering lagging power factor load  (1) the excitation emf leads terminal voltage by the power angle (2) the excitation emf lags terminal voltage by the power angle (3) ... by the power factor angle (4) excitation emf lags the terminal voltage by the power factor angle

Answer : In a synchronous generator delivering lagging power factor load the excitation emf leads terminal voltage by the power angle

Description : The benefit of power factor correction in a power system is (A) lower power consumption (B) increased demand charge (C) reduced load carrying capabilities in existing lines (D) reduced voltage profile

Answer : The benefit of power factor correction in a power system is lower power consumption

Description : The power factor angle and torque angle of a salient pole synchronous generator drawing a current of 1.0 pu from a lagging load are 45o and 15o, respectively. The direct axis and quadrature axis currents, respectively, are (A) 0.5 pu ... pu, 0.5 pu (C) 0.707 pu, 0.707 pu (D) 0.5 pu, 0.5 pu

Answer : The power factor angle and torque angle of a salient pole synchronous generator drawing a current of 1.0 pu from a lagging load are 45o and 15o, respectively. The direct axis and quadrature axis currents, respectively, are 0.866 pu, 0.5 pu

Description : The power factor of a D.C. circuit is always?

Answer : The power factor of a D.C. circuit is always unity.

Description : The ratio of active power to apparent power is known as____ factor.

Answer : The ratio of active power to apparent power is known as power factor.

Description : The input of an A.C. circuit having power factor of 0.8 lagging is 40 kVA The power drawn by the circuit is?

Answer : The input of an A.C. circuit having power factor of 0.8 lagging is 40 kVA The power drawn by the circuit is 32 kW.

Description : Power factor of electric bulb is?

Answer : Power factor of electric bulb is unity.

Description : The power factor at resonance in R-L- C parallel circuit is?

Answer : since a rlc circuit at resonance behaves like a pure resistive circuit, i.e there is no phase difference between current and voltage, hence the power factor is unity.

Description : Power factor of an inductive circuit is usually improved by connecting capacitor to it in?

Answer : Power factor of an inductive circuit is usually improved by connecting capacitor to it in parallel.

Description : Capacitors for power factor correction are rated in?

Answer : Capacitors for power factor correction are rated in kVAR.

Description : Poor power factor?

Answer : Poor power factor reduces load handling capability of electrical system, results in more power losses in the electrical system, overloads alternators, transformers and distribution lines, results in more voltage drop in the line.

Description : Power factor of an electrical circuit is equal to?

Answer : Power factor of an electrical circuit is equal to R/Z, cosine of phase angle difference between current and voltage, kW/kVA.

Answer : The power factor of a single phase load can be calculated if the instruments available are three ammeters or three voltmeters.

Answer : In a dynamometer 3-phase power factor meter, the planes of the two moving coils are at 120°.

Answer : In a single phase power factor meter the phase difference between the currents in the two pressure coils is exactly 90°.

Answer : The two pressure coils of a single phase power factor meter have the same dimensions and the same number of turns.

Answer : A power factor meter has one current circuit and two pressure circuits.

Answer : In a low power factor wattmeter the compensating coil is connected in series with pressure coil.

Answer : In a low power factor wattmeter the pressure coil is connected to the load side of the current coil.

Answer : When a D.C. series motor is connected to A.C. supply, the power factor will be low because of high inductance of field and armature circuits.

Answer : The power factor of a single-phase induction motor is usually lagging.

← Prev Question Next Question →
Ask a Question
Choose topic